 Green Star Technical Clarification Rulings

Technical Clarifications for Green Star represent our answers to Technical Questions submitted by projects, and provide further guidance and reference to others. The list is regularly updated.  

There are two types of Technical Clarifications listed in the table below:

General Clarifications

These are extensions to the guidance provided in the Submission Guidelines. They clarify and sometimes supersede the original Credit Criteria or 
Compliance Requirements. General Clarifications set precedent for future project teams to follow. Should a project team wish to apply a general clarification to its project, there is no requirement for further Technical Questions to be submitted. NZGBC Assessors will also use them as precedents to assess submissions.

Project Specific Clarifications

These are published as references for other projects but, unlike General Clarifications, they do not set precedent. They often relate to special 
situations where multiple prerequisites exist for a particular project and are less likely to reoccur to another project. Therefore, rulings set for Project Specific Clarifications are often conditional and will likely vary for other projects. Each project still needs to submit its own Technical Questions and provides evidence relating to its own building in order to have a similar ruling approved for that specific building. 

Should you wish to apply any Technical Clarification for legacy rating tools to your projects, please submit a Technical Question to the NZGBC to 
explain why and how it applies. You can access the online Technical Question form here

Technical Question Title Tool Version Date Released Credit Name Sub-credit Name TC Link
Daylight Roof Strips in Industrial Projects Green Star Buildings NZ July 2026 11 - Light Quality
Approved Ruling:

For industrial projects, daylight roof strips may be accepted as a compliant alternative solution to the requirement for blinds providing glare reduction across at least 95% of viewing façades and skylights, provided the roof strips are constructed from polycarbonate or a similar translucent or opaque material. Where clear or transparent roof strips are installed, glare control measures or glare modelling must be provided to demonstrate compliance. 

Base Building Contributions for Blinds Green Star Buildings NZ, DABv1, DABv1.1, INTv1.1 September 2026 12 - Visual Comfort, 11 - Visual Comfort Glare reduction
Approved Ruling:
Where blinds are used to meet compliance requirements, they must be provided, either wholly or in part, by the base building owner for both Cold Shell and Warm Shell tenancies as part of the lease agreement. As a minimum, the base building owner is required to provide the blind boxes, or a mutually agreed equivalent value contribution.
Treatment of Electricity in Environmental Declarations Green Star Buildings NZ, DABv1, DABv1.1 September 2026 19 - Life Cycle Assessment/Impacts, 21 - Upfront Carbon Emissions
Approved Ruling:

The attached Technical Clarification document sets out how NZGBC will treat the electricity component of environmental declarations when those declarations are used to substantiate product environmental performance in NZGBC rating tools and databases. It applies to all forms of third-party environmental declaration, including but not limited to Environmental Product Declarations (EPDs) under ISO 14025 and EN 15804, Product Carbon Footprints (PCFs) under ISO 14067, and any equivalent product-level declarations submitted to support rating tool credits.

It addresses the specific question of how electricity consumed in New Zealand is to be modelled and disclosed, and the conditions under which contractual instruments (NZECS certificates, RECs, GOs, I-RECs, or PPAs with bundled environmental attributes) may be reflected in the figures NZGBC uses for rating tool calculations.

This clarification does not change the underlying programme rules of the International EPD System, EPD Australasia, the GHG Protocol Product Standard, ISO 14067, or any other framework. It governs only how NZGBC interprets and uses declared figures for the purposes of its own rating tools.

https://nzgbc.org.nz/hubfs/Treatment%20of%20Electricity%20in%20Environmental%20Declarations.pdf

Acceptable Evidence for VOC and Formaldehyde Compliance Green Star Buildings NZ, DABv1, DABv1.1, Green Star Fitouts, INTv1.1 October 2026 13 - Indoor Pollutants, 13 - Exposure to Toxins, 12 - Indoor Pollutants Indoor Pollutants, Paints, Adhesives, Sealants and Carpets, Engineered Wood products, Paints Adhesives, sealants and carpets, Engineering Wood Products
Approved Ruling:

Three preferred pathways are available for demonstrating compliance with the VOC and formaldehyde requirements for paints, adhesives, sealants and carpets in the relevant toxin and pollutant credits:

    • Elimination
    • Certification under a Recognised Product Certification scheme.
    • Laboratory testing.

Similar requirements also apply to engineered wood products where compliance with specified formaldehyde limits must be demonstrated.

While these remain the preferred pathways, publicly available product information may also be accepted as evidence for this credit.

The following list of documentation is provided as guidance for the Certified submission and is not exhaustive. Project teams are not required to submit all listed items and may provide alternative forms of documentation to demonstrate compliance. The key requirement is that sufficient evidence is provided to demonstrate to a Certified Assessor that outcomes have been met.

Low Toxin Materials Procurement

    • Specifications that demonstrate emission levels or formaldehyde content.
    • Safety Data Sheets that demonstrate compliant emission levels or formaldehyde content.
    • Product toxin test certificates that demonstrate TVOC emission levels or formaldehyde content relevant to the product type.
    • Product certificates that demonstrate certification under a recognised product certification scheme or recognised standard.
    • Invoices or proof of purchase.
    • Finishes schedule or similar summarising all paints, adhesives, sealants, engineered wood products and carpets installed.
    • Environmental Product Declarations (EPDs).
    • Other publicly issued manufacturer documentation.

On-site Testing

    • On-site VOC test results.
    • As built drawings showing the location of the test samples.

Where VOC compliance is being demonstrated, the VOC content of the product must be provided numerically in grams per litre (g/L) of ready-to-use product and clearly demonstrate compliance with the applicable threshold.

Where formaldehyde compliance is being demonstrated, the documentation must clearly state the formaldehyde content, emissions level, or confirm that no added formaldehyde is present, as applicable to the product and criterion requirements.

A statement describing the testing methodology used to determine VOC content or formaldehyde results (for example, the testing standard applied) is no longer required, provided that the submitted documentation clearly demonstrates compliance with the relevant credit requirements.

Potable Water - Fixtures and Fittings exclusions DABv1, INTv1 October 2026 18 - Potable Water Sanitary Fixture Efficiency
Approved Ruling:

For the purposes of the Potable water credit 18B.1, the following fixtures and fittings may be excluded, as the water consumption will not be altered significantly by reducing the water flow: Bath taps, laboratory taps, and interior taps dedicated to cleaning and facility management. Kitchen or café tapware, where the primary use is for pot or container filling. Kitchen/ Café Chilled, Boiling and Sparkling tapware, which are used to fill cups.

Exterior taps, such as hose taps that are used for cleaning buildings and vehicle washing, cannot be excluded from water consumption calculations, as they may account for significant water use.

Alternative Responsible Products Pathway DABv1, DABv1.1 October 2026 20 - Responsible Building Materials, 21 - Sustainable Products
Approved Ruling:

To accelerate market adoption of responsible products and prepare industry for the requirements of Green Star Buildings, projects registered under the Green Star Design & As Built (DAB) rating tool may elect to substitute Credit 20 and Credit 21 in their entirety with an assessment against the following Green Star Buildings Responsible Products credits:

    • Credit 6: Responsible Structure
    • Credit 7: Responsible Envelope
    • Credit 8: Responsible Systems
    • Credit 9: Responsible Finishes

Projects choosing this pathway may then only pursue the suite of Responsible Products credits within Green Star Buildings. This approach is intended to encourage a whole-of-building consideration of responsible products and cannot be used selectively.

Accordingly:

    • Credits 20 and 21 must be fully replaced and cannot be pursued in part alongside any of the Green Star Buildings Responsible Products credits. Project teams cannot combine, substitute, or mix individual Green Star Buildings Responsible Products credits with Credit 20 and/or Credit 21 to optimise point outcomes.
    • Where a building element performs multiple functions, Responsible Product Value (RPV) may contribute towards multiple point outcomes where permitted under the Green Star Buildings credit requirements.

Projects using this pathway may achieve up to 13 points through the Green Star Buildings Responsible Products credits, compared with the maximum 6 points available through DAB Credits 20 and 21.

To maintain the market transformation intent of this pathway, any points achieved above the 6 points otherwise available under DAB Credits 20 and 21 will be recognised through the Innovation category, subject to the Innovation point cap

The intent of this alternative compliance pathway is to promote the specification and procurement of responsible products across multiple building systems.

Energy Use 4 Star Threshold Green Star Buildings NZ 22 - Energy Use
Approved Ruling:

There is a discrepancy in Submission Guidelines for the minimum required energy use reduction for a 4 star certification. The credit shows that there is no increase in minimum reduction from 2024 to 2026 (both state 'meets the minimum expectation'), which would be equal to a 10% reduction. The Carbon Reduction Strategy diagram in the introduction shows this requirement stepping up to 20% in 2026. This is in line with other thresholds increasingover time, and therefore the intended outcome. All projects registering after May 2026 are required to meet a minimum energy use reduction of 20%.

Energy Use Requirements for 4 Star Projects Green Star Buildings NZ November 2026 22 - Energy Use
Approved Ruling:

There is a discrepancy in the Submission Guidelines regarding the minimum energy-use reduction required for a 4 Star certification and the Carbon Reduction Strategy.

In the Strategy table of Credit 22: Energy Use, the requirement for 4 Star projects registering from May 2026 onwards should be amended from "Meets the Minimum Expectation" to "Achieve 1 Point". This means all such projects will be required to demonstrate an energy-use reduction of at least 20% compared with a reference building.

This amendment corrects the text and aligns the credit requirements with the Carbon Reduction Strategy pathway presented in the introduction. The Carbon Reduction Strategy diagram reflects the intended requirement and is consistent with the broader approach of progressively increasing performance thresholds over time.